Type |
Pyrolytic:- Hot Medical Waste Disposing Machine HICLOVER is growing brand for environmental protection field, and market share with most of Africa, Middle East, Southeast Asia countries and part of North America, Europe territory. We are trusted partner for governmental organizations, non-profit organizations, international contractors, logistics organizations, military, pet cremation business owners, etc. We have export experience more than 40 countries, including war zone like Iraq, Afghanistan, Somalia, South Sudan. Mobile: +86-13813931455(WhatsApp) Website: www.hiclover.com Email: sales@hiclover.com Email: hicloversales@gmail.com |
Operation Condition |
8-16 Hr /day |
Controls |
Built in data recording |
Incinerator |
Type: continuous loading |
Capacity/Burn rate per hour: 250 -300kg/hr |
|
Temperature: 900-1200 oC |
|
Material: External- 3 layers Internal lining: a fire proof material of pre-fired refractory bricks with Aluminium lining, resistant to corrosive waste or gas and to thermal shock |
|
Secondary |
Type: horizontal/vertical |
Temperature: 1200-1400 oC |
|
Residence time of gases : >2 seconds |
|
|
Material External- Low thermal mass insulation 14-30 oC Internal lining: a fire proof material of pre-fired refractory bricks with Aluminium nettle lining, resistant to corrosive waste or gas and |
Ash Handling System |
Both Automatic and manual removal of Ash. Must ensure removal/treatment of hazardous remnants of ash. |
Flue gas treatment system |
Capable of treating the flow of flue gas as the incinerator is operating at its maximum capacity |
Auxiliary device: Water level gauge, pressure sensor, PH sensor..etc. |
|
Auxiliary device: Fuel cut off device |
|
Waste feeding mechanism |
Automatic pneumatic/hydraulic waste loading system or conveyor belt , capacity 650-800L at a time |
Chimney (Stack) |
Type: Vertical type |
height: 7-10 meters |
|
Material: Fireproof cast, stainless steel |
|
Wet scrubbing system |
Vertical sprat tower with baffles or packing inside |
Gas emission |
Reduction of Pollutant gas SO2, HCL, HF and line particulate |
OUTPUT |
ASH -Max <5% of original waste size |
GAS- SMOKELESS,ODORLESS |
|
Emission standard |
WHO/ European |
Test report for emission testing |
Must be provided |
Product Data sheet/ Catalogue |
Must be attached to the ITB |
Additional Requirement |
– Local agent or branch in Ethiopia – Training for users as well as for EPHI maintenance staff on preventive maintenance – Fuel tanker with a minimum capacity of 2500 litre (made of plastic material with overfill prevention valve ,fuel gauge, lifting eyes) – The bidder should be willing to sign at least a five years’ service and maintenance agreement with the client (EPHI) – The supplier shall arrange by itself lifting equipment and labour needed during the installation, testing and commissioning of the incinerator |